{}

Merkene våre

Impact-Company-Logo-English Black-01-177x54

Velkommen til nettstedet til Schneider Electric

Velkommen til nettstedet vårt.

Søk i ofte stilte spørsmål (FAQ)

For 115v input ATV12 drives, what should the UnS parameter be set at?

Issue:

For 115v input ATV12 drives, what should the UnS parameter be set at?

Product Line:

ATV12

Environment:

115v input

Cause:

n/a

Resolution:

If the Line voltage is less than the rated motor voltage, the rated motor voltage should

be set to the value of the line voltage, applied to the terminals.

Schneider Electric Norway

Finn ut mer
Rekkevidde:
Altivar 12
Finn ut mer
Rekkevidde:
Altivar 12