How to update SCADAPack x70 RTU BOOTLOADER using PuTTY or Windows Command Prompt
Step 1: Transfer the Bootloader File to the RTU
- Open RemoteConnect and connect to the SCADAPack 47x RTU via USB.
- Enable the Telnet Service on the device.
- Go Online with the device and write the project to the SCADAPack 47x RTU.
- Right-click on SCADAPack x70 Controller Settings – DeviceDTM, then go to:
- Additional Functions > Write File to Device
- In the Write File to Device window:
- Click Browse, locate the bootloader file (e.g., SP47x_BL_151.blz), and click OK.
- Wait for the file transfer to complete.
-
Step 2: Apply the Firmware Patch Using PuTTY
- Open PuTTY and connect to the RTU using the USB IP address:
10.2.3.4. - Type the command: DIR
- This verifies that the bootloader file exists on the device.
- Type the command: RESTART BOOTMON *.blz
- Example:
- RESTART BOOTMON SP47x_BL_151.blz
- Open PuTTY and connect to the RTU using the USB IP address:
- Wait for the firmware patch to complete. The PuTTY session will disconnect automatically.
- Reconnect using PuTTY and type: VER
- This displays the updated bootloader version.
-
Step 3: Apply the Firmware Patch Using Windows Command Prompt
- Open Windows Command Prompt and type: Telnet 10.2.3.4
- This will connect to the SCADAPack x70 RTU.
Type the command: DIR
- This verifies that the firmware file is present.
Type the command: RESTART BOOTMON SP47x_BL_151.blz
- Wait for the patch to complete. The connection will be lost.
- Reconnect using command: Telnet 10.2.3.4
- Type the command: VER
- This displays the updated firmware version.
Publisert for: Schneider Electric Norway
Trenger du hjelp?
Produktvelger
Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.
Be om tilbud
Start din salgsforespørsel online, og vi vil kontakte deg.
Hvor kan du handle?
Finn din nærmeste Schneider Electric-distributør enkelt.
Hjelpesenter
Finn alle nødvendige supportressurser samlet på ett sted.