Why Does the IP Address Reset to 0.0.0.0 After Power Cycling an ATV61 or ATV71 with a VW3A3316 Ethernet/IP Card?

Resolution:
When Forced Local Assignment is assigned to a logic input and that input is active, the IP address and subnet mask may reset to their default value of 0.0.0.0 after the drive is power cycled.

To troubleshoot:

Go to Menu 1.9 [Communication] and check the Forced Local Assignment setting.

When using the VW3A3316 Ethernet/IP option card, verify that Forced Local Assignment is not assigned to a logic input. Then confirm the required IP address and subnet mask settings before power cycling the drive.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings
  • Preference Centre