How can we help you today?

STBART0200 RTD Mode Currents

Issue
This resolution specifies the current injected by the STBART0200 module into an RTD probe.


Product Line
Advantys STB
STBART0200


Environment


Resolution

  • For PT100, Ni100, or CU10 the module injects a 1.25ma current.
  • For PT1000 or Ni1000 the module injects a 0.25ma current.