The REV_XFER EFB will not continue to operate when the Standby PLC goes to an offline condition.
The REV_XFER block is traditionally used in the first executable section of logic. Although the Hot Standby configuration
allows the user to select "Solve First Section" in an offline condition, the REV_XFER will not update the Primary if the
Standby is offline.
In order for REV_XFER to work correctly a valid Standby must exist.
R-91317
Issue: software functionality
Product Line: Quantum 140CPU67160
Environment: Hot Standby
Cause n/a
Resolution: n/a