How to resolve the E5006 failure during Unity application upload.
Question:
Customer met with E5006 failure during Unity application upload. What's the root cause & how to solve it?
Answer:
The application is corrupted in the PLC ( the conf tree is Invalid )
There are 2 ways to restore :
1. If the user has saved correctly the application before ( it seems that it is not the case ) , rebuild all the application to FIX then, download ( using Current Unity Version )
2. The customer (or support ) can use old Unity version to upload application. Then must rebuild all to fix the problem (save to STA ) or export (to XEF) and finally use current version to re open ( STA or XEF )
Customer met with E5006 failure during Unity application upload. What's the root cause & how to solve it?
Answer:
The application is corrupted in the PLC ( the conf tree is Invalid )
There are 2 ways to restore :
1. If the user has saved correctly the application before ( it seems that it is not the case ) , rebuild all the application to FIX then, download ( using Current Unity Version )
2. The customer (or support ) can use old Unity version to upload application. Then must rebuild all to fix the problem (save to STA ) or export (to XEF) and finally use current version to re open ( STA or XEF )
Released for: Schneider Electric New Zealand
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.