How to sync clock to M580 CPU by BMENOC.

Unity Pro must be at a minimum version of 13.0 HF2
BMENOC03x1 must be at a minimum version of 2.12
BMENOC03x1.4 must be selected in the Unity Project.
With all of the above requirements met, in the Services tab of the DTM, with NTP enabled, the Network Time Service settings will include a check box for "Update CPU time with this module:".