What is the difference between the iC60N and the iC60H Circuit Breakers?

The differences between the iC60N and iC60H series of circuit breakers is the iC60N has a breaking capacity of 6kA at 240/415V, C Curve in accordance with AS/NZS60898.1, where as the iC60H has a breaking capacity of 10kA at 240/415V B, C & D Curve in accordance with AS/NZS60898.1.

In Australia the iC60N is only available in C Curve where as the iC60H is available in B, C & D Curve.

iC60N & iC60H Dimensions
 iC60N
Connection: Tunnel terminals for the following cables

- up to 25A : 25mm2 stranded
- 32 to 63A : 35mm2 stranded


For further information please visit https://www.se.com/au/en/product-subcategory/1605-acti-9-miniature-circuit-breakers---mcbs/