Why the M221 PLC is not automatically booting at the end of the Clone operation from SD Card?
A script (script.cmd file) can be generated with SoMachine/Machine Expert Basic (Commissioning >> Memory Management) to create a SD card image within the application (with/without the firmware).
The script.cmd file has such below content (in this case, both firmware and application are selected):
Delete "/usr/cfg"
Delete "/usr/app"
Delete "/sys/os"
Download "/sys/os"
Download "/usr/app"
Download "/usr/cfg"
Reboot
When inserting a SD card into a M221 with the above script file, at the end of the application download, the script executes a “Reboot” command to make the PLC booting and starting with this new application. The M221 PLC behavior would depend on the Boot version it has (Boot is included during manufacturing process, and not updated during a firmware update).
-If the PLC was manufactured with Boot version (it can be read within %SW13) < 28, then the PLC will manage this command. It will reboot and start with this new downloaded application.
-If the PLC was manufactured with a more recent Boot version >=28, then the PLC will reject the "Reboot" command, with an error into the script.log reporting “Reboot - Invalid Command “ and it’s only removing the SD card from the PLC, which will make the M221 automatically reboot.
Released for: Schneider Electric New Zealand
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.