{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Why doesn't the BMXAMO0410 report a channel fault in an open circuit condition?
One common reason is that the "Wiring CTRL" option box for the specific channel has not been selected. If the option is not selected the Channel Fault bit will not sense for open loop. (open ckt).
The ability to detect a broken wire (open circuit) condition is limited to current outputs. The selection is made in the BMXAMO410 configuration screen.



Schneider Electric New Zealand

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: