What needs to be configured in ATV320 when ATV Regen is used?Article available in these languages: Japanese
Dec. Ramp Adapt (BRA) has to be disabled and DC bus chaining (DCCM) has to be set to Bus and Main. If not, SCF3 could appear.
Released for:Schneider Electric New Zealand
Attachment(s)ATV320+regen.png [32.52 KB]