SBO upgrade process failed (SBO 1.8.x to SBO 1.9.x)

Upgrade failed when upgrading Automation Server from SBO version 1.8.x to 1.9.x

Log indicates:
(Device Administrator | View | Last Upgrade Log)
ERROR:        Exception encountered during database upgrade: StartUpMode UpgradeDatabase : RecoverableException: d:\dev\rb-rb-1.9.2-system\source\server\nsp_servers\csc\LonTypes\source\Lon2MapFileUtil.cpp(185) Invalid Data Error: Invalid_Data (0x10000) in module Impex(57). "Map data is too old for type: public.lon2.devicetemplates.pid90003A8200E90401. You need to run the Lon Repair command in the latest version of the workstation"
2019-04-10 07:14:02  INFORMATION:  Database upgrade time: 5.28889 seconds
2019-04-10 07:14:02  INFORMATION:  =============  End Configuration Database Upgrade  =============
Source version: 1.8.1.79 Target Version: 1.9.2.45

Steps
1. Upgrade Workstation and Automation Server to the latest available version (SBO 1.8.1.3600)
2. Connect with Workstation to Automation Server
3. Select Server, and right-click Advanced | Repair LonWorks configuration ...
4. Select Next to repair when indicated "Server needs to be repaired"
5. Finally upgrade to Version 1.9 using Device Administrator

Schneider Electric New Zealand

Attachment(s)
Start repair.PNG.png [120.18 KB]
repair01.PNG.png [37.8 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings