How can we help you today?

How to edit super genies from Graphics Builder

Issue:
To be able to edit super genies

Product Line:

Power SCADA Operations 8.2

Power Operation 2020 and 9.0

Power Operation 2021

Power Operation 2022

Power Operation 2023

Power Operation 2024



Environment:
Graphics Builder

Cause:
When set (the parameter as explained in the 'Resolution' section), enables the user to choose whether or not to open and edit a Super Genie page

Resolution:
Add the following parameter to the INI file (either in Notepad or Setup Editor):

[CtDraw.RSC]
AllowEditSuperGeniePage=1

Recommendation:

If you are using an older version of

Power Operation, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com