Troubleshooting: Micrologic 5.0P or 6.0P or H trip unit will not allow adjustment of the settings on the screen

Issue:
Micrologic Power or Harmonic trip unit won't let me change the on-screen settings.  What is the problem?

Product Line:
Masterpact, Powerpact

Resolution:
The trip unit settings cannot be adjusted via the menu buttons on the trip unit screen unless the trip unit cover (the cover that goes over th dials) is open.