How to deactivate ATVLogic running in ATV320 drive?

The ATVLogic could be deactivated by "Disabling the function" (FBCD) or the logical input that start the ATVLogic Mode (FBRM).

- Set FBCD to STOP, this will deactivate the ATVLogic function:

By keypad:

Go to Drive menu/ Configuration/ Full/ Function blocks, then set FBCD to STOP.
image.png

By SoMove:

Connect the SoMove to the drive, then set FBCD to STOP.
image.png

- Check by keypad or SoMove which logical input (LIx) is set to FB start mode, then disable it.

In the above example, when LI3= OFF, the ATV logic is disabled.