Blue Open Studio Alarm history are not retaining after 24 hours

Issue:

BLUE Open Studio is not retaining ALARMs History after 24 Hours .

Product Line:

Blue Open Studio .

Resolution:

The Alarm Object Properties Filters -> Interval is set to Period by default,

Blue Open Studio Settings

Blue Open Studio Object Properties

Changing the Interval settings to Latest or specify a Period should solve the issue.