How can we help you today?

Smart UPS Modular Ultra Reports Inaccurate Low Runtime

Issue:

My Smart UPS Modular Ultra has reports an inaccurate low runtime on the display/NMC.


Product Line:

Smart UPS Modular Ultra


Resolution:

On UPS Firmware 13.3 or earlier, the runtime may be linked to the battery with the lowest capacity only.  In UPS Firmware 15.0 and later, there is an improvement to the runtime accuracy when a low capacity battery module is installed.

Please install UPS Firmware 15.0 or later.

Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings