How does the M262 FDR function work?

  • FTP server needs to be enabled.

Plc screen1

  • The FDR enabled device (eg. VSD) first needs to upload the parameters via its FDR function to the M262 (FDR server). A FDR parameter file will then be present in the M262 in the Fdr folder.
  • When a new FDR device of the exact same model is connected to the M262 (and replaces the old device), the PLC will automatically transfer the parameters using the FDR parameter file.
  • Note, in the scenario where the FDR device is a SE device (eg. Altivar VSD), uploading the parameters using the DTM in M262 is not the method to allow the FDR function to operate.

Schneider Electric New Zealand

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software and Firmware
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Where to Buy?
  • Office Locations
  • Schneider Electric, PDL & APC Phone: 0800 741 303
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Conditions of Sale
  • Change your cookie settings