How to Auto Start Windows pre-installed Runtime HMI (HMIG5U ,HMIG5U22, HMIGTW7353 ,..etc) after Power Cycle
Issue:
After downloading the Project file to Windows pre-installing Runtime HMI , power cycle the HMI and its asking
If I click in “Continue” is running the application , but shouldn’t it be automatic?
Product Line:
HMIG5U/HMIG5U2/HMIG5U22/HMIGTW7353 .
Resolution:
Please Click on "Lock" in the above image and restarting the HMI will enable the Write Filter ,then the Target Runtime will Start Automatically.
NOTE:
If you want to Shut down the Vijeo Runtime that is running automatically after Power-up , then Please use an External Keyboard and press Alt + Ctrl + Delete ,and then go to Task Manager to Close the Vijeo Runtime .
Released for: Schneider Electric New Zealand