How to obtain a digital output signal (dry contact) from Micrologic 5.0X Ground-Fault Alarm on MTZ2,

With a 3-pole, 4000A, MTZ2 40H2 100kA Drawout Schneider MasterPact ACB fitted with a Micrologic 5.0X trip unit, and willing to enable the Ground-Fault Alarm (ANSI 51N/51G) function on this trip unit.

It is possible to obtain a digital output signal (dry contact) from the MTZ2 for this Ground-Fault Alarm using the M2C programmable contacts module.