What is the accuracy of the RM17TU00 adjustment under voltage setting?

Goals and Symptoms

If I set the voltage to 208V nominal, then I set the under voltage trip point at -5%, that's = 198V. What it the accuracy of the 198V under voltage setting? Does the relay trip anywhere in between 178V-218V?? (+-10% of 198V ???)

Facts and Changes

accuracy of dropout when set for a particular percentage.
RM17TU00

Causes and Fixes

The accuracy of a voltage setting is given in catalogue by the "setting accuracy" characteristic. It is the accuracy of the potentiometer position according to the marking on the front face.
Example:
Set the potentiometer at -10% (with Un= 208V => 187V), then the real voltage setting will be between 9% and 11% of Un(185V and 189V), +/-10% of 10.

Schneider Electric Portugal

Explorar mais
Gama:
Explorar mais
Gama:

Precisa de ajuda?

Precisa de ajuda?

Ferramenta de seleção de produtos

Ferramenta de seleção de produtos

Encontre rápida e facilmente os produtos e acessórios certos para as suas aplicações.

Obter um Orçamento

Obter um Orçamento

Inicie o seu pedido de contacto online e um especialista irá contactá-lo.

Onde adquirir?

Onde adquirir?

Encontre facilmente o distribuidor mais próximo da Schneider Electric perto de si.

Centro de ajuda

Centro de ajuda

Encontre recursos de apoio para todas as suas necessidades, num único local.

  • Documentação dos Produtos
  • Transferências de Software
  • Ferramenta de Seleção de Produtos
  • Substituição e Troca do Produto
  • Centro de Ajuda e de Contacto
  • Encontre os nossos escritórios
  • Obter um orçamento
  • Onde adquirir
  • Comunidade Schneider Electric
  • Carreiras
  • Perfil da empresa
  • Comunicar uma má conduta
  • Acessibilidade
  • Newsroom
  • Investidores
  • EcoStruxure
  • Pesquisa de emprego
  • Blogue
  • Política de privacidade
  • Aviso sobre Cookies
  • Termos de utilização
  • Alterar suas configurações de cookie