It is only possible to use Blokset DC voltage values lower than 1000V. In this DC network case, design & manufacture the Blokset according to the technical specification and mounting rules of AC current. Same rules apply as for AC networks (size of compartments, busbars cross-sections, size of cables, etc.)
-
- Regarding switchgear (MCCBs, ACBs)
Their DC version can also be assembled inside of Blokset.You can use Compact NS for DC in fix-type unit or withdrawable units, as it has the same size as NS for AC: no changes is required (while using 3 poles circuit breaker). The precaution to take are linked to voltage level and the grounding type (this can lead to use NS DC from 2-pole to 4 pole). The Compact NS catalogues give all information about how to choose the right Compact NS or Masterpact for this application. Catalogues can be found in "15 More about Schneider Electric PRODUCTS" (latest transfer file version).
When necessary to use 2 or 4 poles circuit breakers, size of the drawers may need to be adapted. In any case, the compartment size must be the same as for an AC compartment of the same power/current rating.
- Regarding switchgear (MCCBs, ACBs)
Legacy KB System (APS) Data: RESL190682 V2.0, Originally authored by JoElRe on 01/17/2008, Last Edited by GwPo on 06/25/2010
Related ranges: Blokset
Publicado para: Schneider Electric Portugal
Precisa de ajuda?
Comece aqui!
Encontre respostas agora. Procure uma solução sozinho ou entre em contacto com um dos nossos especialistas.
Contactar a assistência
Contacte a nossa equipa de atendimento ao cliente para receber mais informações, assistência técnica, assistência com reclamações e muito mais.
Onde adquirir?
Encontre facilmente o distribuidor mais próximo da Schneider Electric perto de si.
Consulte as perguntas frequentes (FAQ)
Obtenha as respostas de que necessita explorando as perguntas frequentes (FAQ) relacionadas com tópicos.
Contactar o departamento de vendas
Inicie o seu pedido de contacto online e um especialista irá contactá-lo.