Why do I see 115 VAC on the outputs of the BMXDAO1605 when there is no load connected to to module?
Issue:
Why do I see 115 VAC on the outputs of the BMXDAO1605 when there is no load connected to to module?
Product Line:
BMXDAO1605
Resolution:
This is normal when attempting to measure a triac output with no load. Triac outputs cannot be accurately tested without a load.
The high impedance of the voltmeter will introduce enough of a load to cause the applied voltage on the triac to be seen.
Test with a load applied to the triac and you'll get a more meaningful measurement.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.