{}

As nossas marcas

Impact-Company-Logo-English Black-01-177x54

Bem-vindo ao website da Schneider Electric

Bem-vindo ao nosso site.

Pesquisar nas perguntas frequentes (FAQ)

How can I set up an ATV61/71 Drives to run reverse using Ethernet IP with assemblies 103 and 104?

Issue:
Setting up ATV61/71 drives to run reverse using Ethernet IP with assemblies 103 and 104?

Product Line:
Altivar ATV61 and ATV71 with Ethernet IP card VW3A3316

Environment:
All

Cause:
Needs to write a reverse command over the network using assemblies 103 and 104.

Resolution:
Ethernet IP command for REV  using assemblies 103 and 104.
Reverse mode
bits 1, on
bits 5 on
bits 13 on
all need to be on
bit 4 needs to be off
or DEC 8226 is REV

Schneider Electric Portugal

Explorar mais
Explorar mais