Issue:
ATV312 not changing from local to remote mode.
Product Line:
ATV312 series drives
Environment
Firmware version 5.1 IE56 and above.
Cause:
Recent firmware change.
Resolution:
As of firmware version 5.1 IE56, The ATV312 series drives can no longer be switched from local mode to remote. In order to change the drive from local to remote, you perform a factory reset using the FCS parameter.
ATV312 not changing from local to remote mode.
Product Line:
ATV312 series drives
Environment
Firmware version 5.1 IE56 and above.
Cause:
Recent firmware change.
Resolution:
As of firmware version 5.1 IE56, The ATV312 series drives can no longer be switched from local mode to remote. In order to change the drive from local to remote, you perform a factory reset using the FCS parameter.