{}

As nossas marcas

Impact-Company-Logo-English Black-01-177x54

Bem-vindo ao website da Schneider Electric

Bem-vindo ao nosso site.
Pesquisar nas perguntas frequentes (FAQ)
TM251MESE : Modbus TCP IOscanner channel status can be wrong
With TM251MESE firmware v4.0.4.14, when using Modbus TCP IO scanner with more than 16 channels, channels health bits may be wrong.

Firmware v4.0.5.10 (available with SoMachine v4.2) solves this issue.

Schneider Electric Portugal

Explorar mais
Gama:
Artigos que possam ser úteis
Explorar mais
Gama: