How many SCADA clients can be connected to an Easergy T300 using IEC 104 protocol?

  • There is a limitation of 8 redundant connections to create multiple SCADA channels using the IEC104 protocol. Create 1 channel per client.
  • Make sure to fill-in the Remote IP@ list field. It shall be different for every channel
  • Please refer to attached file