Video: How do I use an external PT100 RTD for Cold Junction Compensation (CJC) on the BMXART0814?
Issue:
How to configure an external PT100 RTD for Cold Junction Compensation for the BMXART0814.
Product Line:
BMX IO
Resolution:
It is possible to use a single PT100 RTD for CJC on all eight channels of the BMXART0814.
The user can configure the BMXART0814 for "Temperature from Ch 4 - 7 & External PT100 " in the module's configuration page.
The external PT100 RTD must be placed across Exe + & Exe - of Channel 4 of the BMXART0814.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: