Como o podemos ajudar hoje?

Which kind of ethernet cable shall I used for cabling a remote I/O ethernet architecture on M580 configuration .

Schneider-Electric recommends the use of SFTP (Shielded and Foil Twisted Pair) Cat5e or Cat6 (10/100 Mbps) cables, especially the cables listed below :

  • TCSECN3M3M••••: Cat 5E Ethernet straight-through shielded cable, rated for industrial use,,CE- or UL-compliant
  • TCSECE3M3M••••: Cat 5E Ethernet straight-through shielded cable, rated for industrial use, CE-compliant
  • TCSECU3M3M••••: Cat 5E Ethernet straight-through shielded cable, rated for industrial use, UL-compliant

These kind of cables are compliant with industrial applications and increase the robustness of the application against potential EMC disturbances.

You can also consult EMC and Shielding guide documentation Country Selector | Schneider Electric Global or by searching "EIO0000006047" in se.com