Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Which power phases are controlled by Altistart 01 Soft-Starter?

Article available in these languages: Finnish

The power phases that are controlled by Altistart 01 Soft-Starter are as follows:

In N1 Range of Altistart 01 Soft-Starter only 1 Phase is controlled and that is L1, L2 and L3 are uncontrolled.
In N2 Range of Altistart 01 Soft-Starter only 2 Phases are controlled and that is L2 and L3, L1 is uncontrolled.

Schneider Electric Saudi Arabia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings