{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Is it necessary to use the protection shield on the top side of the Compact NS>630 if the breaker is mounted in horizontal position.
The white protection shield at the top side of the breaker is for protection and isolation of the bare cable connectors against gas exhaust.
Hence it is always necessary to use protection shield irrespective of the breaker mounting position.
Note: It is not necessary at the down side because the hot gas exhaust is always from the top.

Schneider Electric Saudi Arabia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: