How can I change the EWS service in Power Monitoring Expert to use a port other than port 80 (the default)?
Issue:
Customer would like EWS service to run under a different port other than the default port 80.
Product Line:
Power Monitoring Expert 7.2
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment:
EWS Server Configuration
Cause:
Customers can have specific needs to have EWS running under a custom port instead of the default port 80.
Resolution:
Changing the Port number for the EWS service:
- Open IIS by entering the “inetmgr” in the RUN command and enter.
- Remove the existing Web application from the IIS.
- Create new Website for the EWS service:
- Enter the Site name as EWS and select the EWS path($\Schneider Electric\ION Enterprise\Applications\EWS) in the Physical path section and enter the unused port number, as per the following screenshot:
- Select the Advanced settings of the EWS Website.
- Select the Application pool as “Application Modules AppPool” as per the following screenshot.
- Browse the DataExchange.svc.
- On browsing the EWS service, the user will be prompted to enter username & password. Enter the PME username & password.
- Copy the EWS service URL from the browser (Address bar) and update the Web.config file from the following location ($\Schneider Electric\ION Enterprise\Applications\EWS).
Replace the existing URL as given in the following screenshot with the copied URL from the browser.
Now the EWS service works with the new port number configured in the new EWS website.
Released for: Schneider Electric Saudi Arabia
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.