Bandwidth limitation on the service port of 140NOC78100
Issue

What is the limitation on the service port of a 140NOC78100?

Product Line

Quantum, 140NOC78000

Resolution

According to the product spec, port 1 (service port) has ingress rate limiting as follows:

  • Unknown unicast, broadcast rate limit = 500 pps
  • Arp rate limit = 500 pps
  • Multicast rate limit = 30%
  • known unicast rate limit = 30%