Pulse output is used for active energy pulse output only. You can configure the pulse
frequency (pulse/kWh) and the pulse width. The minimum pulse width is 50 ms. The
pulse stop is equal or longer than the pulse width. The pulse output indicates the
primary energy consumption considering transformer ratios. You should set a proper
value of pulse frequency and pulse width to avoid pulse missing due to over-counting.
frequency (pulse/kWh) and the pulse width. The minimum pulse width is 50 ms. The
pulse stop is equal or longer than the pulse width. The pulse output indicates the
primary energy consumption considering transformer ratios. You should set a proper
value of pulse frequency and pulse width to avoid pulse missing due to over-counting.