RJ-45 to SCADAPack Vision
This cable is used to connect from the COM3 (RJ-45-based RS-232) port on the RTU to a DE-9S connector on a SCADAPack Vision. A 1.5 m (5 ft.) long cable is available from Schneider Electric using part number TBUM297237.
RJ-45 to SCADAPack Vision cable Description
RJ-45 | SCADAPack E Function | SCADAPack Vision Function | DE-9S |
Shield connects to shell | |||
6 | TxD | RxD | 2 |
5 | RxD | TxD | 3 |
4 | GND | GND | 5 |
3 | DTR / Test 2 | ON switch | 1 |
2 | DCD / Test 1 | ON switch | 4 |
1 | +5 Vdc Out | +5 Vdc In | 9 |
7 and 8 are not connected at this end. | Wires not connected at this end. |