{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
I need the waveform disturbance recording for Io without core balance CT connected, how can I do?
Use so called Holmgren or sum connection  instead of IoCalc mode and choose measured Io as channel.

Schneider Electric Saudi Arabia

Attachment(s)
sum connection.JPG.jpg [16.39 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: