{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What causes a PID Feedback Error on an Altivar Process Drive?
Issue:
My Process drive tripped and shows PFMF PID Feedback Error

Product Line:
Altivar Machines, Altivar Process Drive

Environment:
All models and serial numbers

Cause:
Programming configuration

Resolution:
Rapid changes in flow like a Valve opened, so it will run full speed.  While valve remains open the drive shuts down on PFMF PID Feedback Error, because the loop is now open.  Go to Pump Functions Feedback Monitoring Feedback Monitoring and change to NO.

Schneider Electric Saudi Arabia

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: