Easergy MiCOM P14x relay is hanging when injecting three-phase current above 0.25 A, but works fine with single-phase injection. How can this be resolved?

Issue/description:

Easergy MiCOM P14x relay is hanging when injecting three-phase current above 0.25 A, but works fine with single-phase injection.

Product family:

Easergy  Micom P14x relays

Resolution:

Please check no gap detection on/off. & disable no gap detection from the event record in the Record Control in the Easergy  Micom device to solve this issue.

Kindly find attached the snapshot how to reach no gap in Micom P14x relays.

If you require any further assistance, please contact our Customer Care team.
Local Customer Care support contact details can be found at the following Schneider Electric link:
https://www.se.com/eg/en/work/support/customer-care/contact-schneider-electric.jsp

Schneider Electric Saudi Arabia

Attachment(s)
Px4x_No gap unselect _procedure.JPG.jpg [37.53 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Product Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Centre
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings