Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error

Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
- Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
- Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
Released for: Schneider Electric Saudi Arabia
Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error

Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
- Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
- Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
Released for: Schneider Electric Saudi Arabia




Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales enquiry online and an expert will connect with you.