Is it possible to activate two setting groups in MICOM P116 model A and model L? How can we activate them? How can we switch between the two groups?

Issue:
Customer has MICOM P116L and wants to activate two setting groups.

Environment:
MICOM P116 settings

Resolution:
Having two setting groups option is available only in MICOM P116 model A (P116A). MICOM P116 model L (P116L) has only one setting group and can not be upgraded nor modified in order to add the two setting groups option since it has a different hardware from that of model A.

Below extract from the manual shows how to activate the two setting groups option in P116A and how to switch between them.