Våra varumärken

Impact-Company-Logo-English Black-01-177x54

Välkommen till Schneider Electrics webbplats

Välkommen till vår webbplats.
		
Hur kan vi hjälpa dig idag?
What can cause an Internal Error 10 on the ATS480 soft start?

Issue:

What can cause an Internal Error 10 on the ATS480 soft start?

Product Line:

ATS480

Environment:

INF10 fault

Cause:

n/a

Resolution:

Would suggest to power down the soft start and recheck all the internal connections.

This error is triggered if the external +24vdc supply voltage is higher than 30v, or lower than 19v.

This fault can also occur if the 24v output current is greater than 200ma.

Measure the +24v to com on the soft start.

Check the +24Vdc supply or the current requested by the load connected to the output +24

Recheck the wiring: Previous wiring of ATS48 (+24 and LO+) is at the same location (+24 and 0V) for ATS480.

Do not connect LO+ from ATS48 to 0V of the ATS480.

Schneider Electric Sverige

Utforska mer
Produkt:
Utforska mer
Produkt:

Behöver du hjälp?

  • Produktväljare

    Hitta snabbt och enkelt rätt produkter och tillbehör för dina ändamål.

  • Begär en offert

    Ställ din fråga online så kontaktar vi dig.

  • Här köper du

    Hitta enkelt närmaste Schneider Electric-distributör på din ort.

  • Hjälpcenter

    Hitta alla supportresurser som du behöver på ett ställe.

  • Produktdokumentation
  • Ladda ner programvara
  • Produktväljare
  • Byt ut eller ersätt produkt
  • Hjälp- och kontaktcenter
  • Här köper du
  • Begär en offert
  • Hitta våra kontor
  • Shop.se.com/se/sv nedstängning
  • Karriär
  • Företagsprofil
  • Rapportera ett tjänstefel
  • Tillgänglighet
  • Pressrum
  • Investerare
  • EcoStruxure
  • Sök jobb
  • Blogg
  • Sekretesspolicy
  • Cookie-information
  • Användarvillkor
  • Change your cookie settings