IDP05S 2-Point Calibration
  1. Press NEXT three times and CALIB will be displayed
  2. Press ENTER and CAL ATO will be displayed
  3. Press Next and CAL LRV will be displayed
  4. Apply the lower range value pressure to the transmitter
  5. Press ENTER and CALWAIT will be displayed
  6. After 10-15 seconds, LRVdone will be displayed
  7. Press NEXT and CAL URV will be displayed
  8. Apply the upper range value pressure to the transmitter
  9. Press ENTER and CALWAIT will be displayed
  10. After 10-15 seconds, URVdone will be displayed
  11. Press NEXT until SAVE is displayed
  12. Press ENTER
  13. Complete