Issue:
ATV340 voltage trip levels.
Product line:
ATV340, Altivar 340
Environment:
480V models
Cause:
High line voltage, regeneration
Resolution:
The trip level for Overbraking is 820VDC on the DC bus.
Overbraking threshold is 780VDC on the DC bus.
The trip level for Mains Overvoltage is 760VDC on the DC bus.
ATV340 voltage trip levels.
Product line:
ATV340, Altivar 340
Environment:
480V models
Cause:
High line voltage, regeneration
Resolution:
The trip level for Overbraking is 820VDC on the DC bus.
Overbraking threshold is 780VDC on the DC bus.
The trip level for Mains Overvoltage is 760VDC on the DC bus.