Issue:
There is likely an issue will be encountered while trying to upgrade the UPS FW over the web interface
Product Line:
SRTL3KRM1UNC, SRTL3KRM1UC, SRTL2K2RM1UNC and SRTL2K2RM1UC
Environment:
All part numbers, all serial numbers
Resolution:
It is recommended to use SCP or SSH if upgrading the UPS firmware remotely. Please see the following steps for the procedure.
Steps
- Use “scp” to transfer firmware image file to root folder of NMC. For example: “scp <image_file> <username>@<NMC_ip_address>:\<image_file>”
- Use ssh to log into NMC, issue “upsfwupdate -install -file A:\<image_file>” command to start upgrading UPS firmware.
Example
- NMC IP address is 10.191.15.107
- Username is apc.
- Image file: SRTL1034UPS_06-7.enc (could be different depending on UPS ID and FW you are uploading)
- OS: Windows 10
C:\fw_image>dir Volume in drive C is Windows Volume Serial Number is C0FF-E65A Directory of C:\fw_image 09/19/2024 05:06 PM <DIR> . 09/19/2024 05:06 PM <DIR> .. 08/14/2024 08:56 AM 1,601,152 SRTL1034UPS_06-7.enc <- firmware image file on local PC. 1 File(s) 1,601,152 bytes 2 Dir(s) 240,162,951,168 bytes free C:\fw_image>scp SRTL1034UPS_06-7.enc apc@10.191.15.107:\SRTL1034UPS_06-7.enc <- transfer file to NMC. apc@10.191.15.107's password: SRTL1034UPS_06-7.enc 100% 1556KB 161.6KB/s 00:09 C:\fw_image>ssh apc@10.191.15.107 <- ssh into NMC. apc@10.191.15.107's password: Schneider Electric Network Management Card AOS v2.5.0.8 (c) Copyright 2023 All Rights Reserved Smart-UPS APP v2.5.0.6 ------------------------------------------------------------------------------- Name : apc753330 Date : 09/19/2024 Contact : Unknown Time : 17:08:13 Location : Unknown User : Super User Up Time : 1 Day 6 Hours 44 Minutes Stat : P+ N4+ N6+ A+ ------------------------------------------------------------------------------- IPv4 : Enabled IPv6 : Enabled Ping Response : Enabled ------------------------------------------------------------------------------- HTTP : Disabled HTTPS : Enabled FTP : Enabled Telnet : Disabled SSH/SCP : Enabled SNMPv1 : Disabled SNMPv3 : Disabled Modbus TCP : Disabled BACnet/IP : Disabled ------------------------------------------------------------------------------- Super User : Enabled RADIUS : Disabled Administrator : Disabled Device User : Disabled Read-Only User : Disabled Network-Only User : Disabled Type ? for command listing Use tcpip command for IP address(-i), subnet(-s), and gateway(-g) apc>dir <- check the file is uploaded to root folder. E000: Success 1024 May 12 2023 apc_hw21_aos_2.5.0.8.bin 6795900 May 12 2023 apc_hw21_su_2.5.0.6.bin 45000 Sep 19 17:08 config.ini 0 Jul 22 2023 db/ 0 Jul 22 2023 ssl/ 0 Jul 22 2023 ssh/ 0 Jul 22 2023 logs/ 0 Jul 22 2023 sec/ 0 Jul 22 2023 fwl/ 0 Jul 22 2023 email/ 0 Jul 22 2023 eapol/ 0 Jul 22 2023 certs/ 0 Jul 22 2023 tmp/ 0 Jul 22 2023 upsfw/ 1601152 Sep 19 17:07 SRTL1034UPS_06-7.enc <- Firmware has been uploaded to root folder. apc>upsfwupdate <- Print the help of upsfwupdate command. E102: Parameter Error Usage: upsfwupdate -- Initiate UPS Firmware Update upsfwupdate <-install <-file filepath | -ver versionspec> [-progress bar] | -list (list available FW versions) -status [-progress bar] | -lastresult | -info <-file filepath | -ver versionspec>> -- Examples: -- Get information about version 1.8: -- apc> upsfwupdate -info -ver "ID18UPS 1.8" -- Install an update from the USB drive: -- apc> upsfwupdate -install -file "C:\upsfw\SMT18UPS_09-1.enc" -- Note: File paths refer to drives attached to the NMC. apc>upsfwupdate -install -file A:\SRTL1034UPS_06-7.enc <- Install UPS firmware. E000: Success |
Note
- If you encounter “scp: Connection closed” error as shown below when you use scp command to transfer firmware image file to NMC, you need to add “-O” option.
C:\fw_image>scp SRTL1034UPS_06-7.enc apc@10.191.15.107:\SRTL1034UPS_06-7.enc apc@10.191.15.107's password: scp: Connection closed |
Example of adding “-O” option to force using the original SCP protocol.
C:\fw_image>scp -O SRTL1034UPS_06-7.enc apc@10.191.15.107:\SRTL1034UPS_06-7.enc apc@10.191.15.107's password: SRTL1034UPS_06-7.enc 100% 1556KB 161.6KB/s 00:09 |
This is the description of “-O” option.
Other Information
- If want to install OpenSSH on Windows system, you can follow the instructions described in this link - Installing and Enabling OpenSSH on Windows.
- If you need to download the firmware for SRTL3KRM1UNC, SRTL2K2RM1UNC units, you can download it from this link - https://www.se.com/us/en/download/document/SPD_CLII-AXFCNC_EN/.
Released for: Schneider Electric Singapore
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.