{}

Markalar

Impact-Company-Logo-English Black-01-177x54

Schneider Electric Web Sitesine Hoş Geldiniz

Web sitemize hoş geldiniz.
SSS'leri Arayın
Why are all LED's flashing simultaneously on my Smart-UPS SU, SUA, or SURT model?

Article available in these languages: İspanyolca


Issue:

LED's flashing simultaneously

Product Line:

Smart-UPS

Environment:

All non-LCD display models (Line Interactive and Online), All Serial Numbers

Cause:

All LED's, or the two center columns of LED's flashing simultaneously generally indicates a hardware failure.

Resolution:

Try to reset the fault by turning the UPS off/on or by performing a "brain dead" on the unit. To perform a "brain dead":
  • Turn off the UPS
  • Unplug the UPS from utility power
  • Press and hold the off button again - You will hear a "click" and may see a brief flash of the LED's
If this fails to clear the fault, contact APC Support for further assistance.

Schneider Electric Turkey

Schneider Electric Türkiye ile İlgili Ürünler
Seri:
Yardımcı olabilecek makaleler
Schneider Electric Türkiye ile İlgili Ürünler
Seri: