Is there a way to get more torque out of the motor when running at lower speeds with an ATV312 drive?
Issue:
How to increase the torque out of a motor when running at lower speeds with an ATV312 drive
Product Line:
ATV312
Environment:
All
Cause:
More torque
Resolution:
First, verify that the motor data is correct in the drC menu. Then set UFt to L. In the SEt menu, increase UFr to provide higher torque output.
How to increase the torque out of a motor when running at lower speeds with an ATV312 drive
Product Line:
ATV312
Environment:
All
Cause:
More torque
Resolution:
First, verify that the motor data is correct in the drC menu. Then set UFt to L. In the SEt menu, increase UFr to provide higher torque output.