我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How do I change the Profibus address on the ATV61 or ATV71 with an optional Profibus card?
Issue:
ATV61 or ATV71 change of the Profibus address with the optional Profibus card.

Product Line:
Altivar 61, Altivar 71

Environment:
Profibus network

Cause:
Configuration

Resolution:

Profibus card part numbers are VW3A3307 or VW3A3307S371.

The profibus address is set through a series of 8 dip switchs on the card beside the 9 pin profibus connector.  The address is set in binary form.  A switch in the up position indicates 0 and in the down position indicates 1.  The least significant bit is the far right switch. Example, to set the address to 36 (binary 00100100).  Place the switches in order from left to right: UP, UP, DOWN, UP, UP, DOWN, UP, UP.

Profibus option card photo 1

Refer to page 11 in either of the attached Profibus manuals for switch configurations. You can also download the manuals using these links:

ATV61/71 Profibus DP manual - VW3A3307
https://www.se.com/us/en/download/document/1755873/

ATV61/71 Profibus DPv1 manual - VW3A3307S371:
https://www.se.com/ww/en/download/document/AAV52935/

施耐德電機Taiwan

附件
ATV6171 Profibus DP manual - VW3A3307 1755873.pdf [439.59 KB]
ATV61_71_PROFIBUS_DPv1_EN_AAV52935_02.pdf [597.24 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings