On the enclosed E-Flex drives why is the yellow fault LED turned on all the time when the drive is not running or when its in bypass mode?
Issue:
Yellow fault led is illuminated on the front cabinet when the drive is not running and when the motor is running in bypass mode.

Product Line:
ATV61 E-flex enclosed systems.

Environment:
All E-flex systems with Modification B09 , All serial numbers.

Cause:
Line side isolation contactor (modification B09) remains open until a run command is issued.  This is by design.

Resolution:
This is normal Operation for an E-flex system equipped with a Line Side Isolation contactor.  The fault indicator lamp is controlled via the R1 fault relay in the drive.  This is a active low fault indication so the lamp will be powered any time the relay is not energized.  The drive is not powered until a run command is issued.  Once the run command is issued, the Line Side Isolation Contactor closes, providing power to the drive and the fault indication lamp.   The drive must fully boot and sense that no fault is present before it will power the fault relay. This takes a few seconds from the time the drive is powered and during that time, the fault indicator lamp will be lit.
Refer to the E-Flex instruction manual 30072-451-51D wiring diagrams page 80.

施耐德電機Taiwan

附件
30072-451-51.pdf [5.87 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings