What would cause the ATV312 display to flash?
Issue:
Drive's display is flashing.

Product Line:
ATV312

Environment:
All

Cause:
Drive display blinks off and on.  Motor does not reach commanded speed.  Drive may eventually shuts down with Motor Overload Fault (OLF) or Drive Over Temp Fault (OHF).

Resolution:
The blinking or flashing display is a warning indication that the motor is pulling the maximum current limit programmed value in the drive which is set by the CLI [Current Limitation] parameter in the SEt- menu as the image below.
CLI atv312
  • Check your load to see if motor direction is correct. If the motor is spinning too fast in the wrong direction, the drive will have a difficult time catching it and correcting the direction. In this case, a mechanical brake on the motor may be necessary
  • See if motor is stuck or in a locked rotor.
  • Check the drive settings (drC- menu) to be sure the motor nameplate information is entered correctly (UnS, FrS, nCr, nSP, COS)
  • Check your the Set- menu to be sure ItH (motor thermal current - Overload protection) and CLI (Current limitation) are set properly.
  • Measure motor current draw.

Please note the main display on the drive will flash the frequency hz value on and off when its in current limit mode.
The remote HMI VW3A1101 will show CLI in the upper left corner of the HMI if its in Current Limit.

See the ATV312 Programming Manual for further details:
https://www.se.com/us/en/download/document/BBV46385/

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings