What is the maximum current value which can go through CSH30 primary (P1-P2)?
Product Line
CSH30
Resolution
Withstanding characteristics of CSH30 are:
Continuous overload : 300 A primary
1 second overload : 12.5kA primary
Limiting dynamic value : 32kA peak (one time)
Within these limits Sepam will continue to work properly.